Seat Valve pneum. force pilot
Series D2602/04.. - D2612/03
Valve D2609/0402/8008-EN
Externally controlled and forced pilot operated valve. In the rest position, the valve is closed by spring and medium pressure. The actuator pressurised with pilot pressure opens a pilot bore and lifts the piston from the main seat directly or assisted by the pressure difference. Valves of this design can also be supplied with the function opened by spring force. There is also a double-acting piston actuator.
For more information follow this link:
Valve D2609/0402/8008-EN
Datasheet explicit
Datasheet universal
datasheet 26-04
Instructions
Manual - Valves electropneumatic (DE/EN)
Version | D | |
Type of valve | 26 | Seat Valve pneum. force pilot |
Connection type, valve seat | 09 | DN100 100mm |
Kv-value (Δp = 1 bar H₂O) | 125 m³/h | |
Housing | 04 | EN-GJL250 grey cast |
Sealing | 02 | FKM |
Function | 8 | OPEN with spring |
Design | 0 | straight seat, actuator aluminium |
Actuator size | 08 | ⌀80 |
Actuator volume | 260 cm³ | |
Valve option | EN | Sensor inductive, 1-fold |
System pressure | 0 - 16 bar (the max. operating pressure requires a control pressure of min. 6 bar) | |
Control pressure | 4 - 10 bar | |
Temperature Medium | from -10 °C to 140 °C | |
Temperature Environment | from -10 °C to 60 °C | |
Mounting position | in any position | |
Specific use case | Closed system (includes open system) | |
scope of delivery | 1 valve |
Not applicable
Valve option | EN | Sensor inductive, 1-fold |
Description | Inductive sensor for position indication | BJ standard, round M12x1.5, in the bracket, requires customer information whether OPEN or CLOSED | |
REACH-RoHS conformity | REACH Yes | RoHS Yes | |
Customs export | Customs tariff number 84812090; Country of origin Germany; ECCN (US): N; AL: N |