Seat Valve electr. direct
Series 23-08-EN161
Valve A2309/0802/5104-CH AC
Solenoid valves as safety shut-off devices class A, group 2 according to DIN EN161 with EU type examination EU/2016/426 are used as automatic shut-off valves for securing, limiting, shutting off and releasing the gas and air supply at main shut-offs or in front of gas burners. The valves are suitable for the following gases: Gases corresponding to gas families according to DIN EN 437, gases of the 1st, 2nd and 3rd gas family according to G260.
For more information follow this link:
Valve A2309/0802/5104-CH AC
Datasheet explicit
Datasheet universal
Datasheet A23-08 EN161
Version | A | |
Type of valve | 23 | Seat Valve electr. direct |
Connection type, valve seat | 09 | DN100 100mm |
Kv-value (Δp = 1 bar H₂O) | 145 m³/h | |
Housing | 08 | AISI 316 - 1.4408 |
Sealing | 02 | FKM |
Voltage type | 5 | AC |
Solenoid power | 10 | 900/70W |
Protection class | 4 | Ex protection |
Valve option | CH | normally closed + EN161 - Gas EU type examination | normally closed + EN161 gas approval, SIL2 |
System pressure | 0 - 10 bar | |
Valve type | 12V, 24V, 48V, 110V, 120V, 220V, 230V, AC | |
Temperature Medium | from -10 °C to 60 °C | |
Temperature Environment | from -10 °C to 60 °C | |
Mounting position | Actuator in vertically or horizontal position | |
Specific use case | Closed system (includes open system) | |
scope of delivery | 1 valve, 1 Solenoid | 900W pickup- | 70W holding winding | M20x1,5 | Valve Control TS1500 | II3G Ex nA IIC T3 Gc (Zone 2) | |
Valve option | CH | normally closed + EN161 - Gas EU type examination | normally closed + EN161 gas approval, SIL2 |
Description | Valve opens with continuous voltage | EC-type aproval with product ident-no. and CE-Marking in conformance with EC-Gas Appliances Regulation (EU/2016/426) | |
REACH-RoHS conformity | REACH Yes | RoHS Yes | |
Net weight | 145 kg | |
Customs export | Customs tariff number 84818079; Country of origin Germany; ECCN (US): N; AL: N |
Not applicable