Solenoid valves
October 2023

Servicing high pressure solenoid valve in the pump station

Valves are to be maintained according to their use and stress involved. Stress is based on the operation time, medium, pressure, and exceptional circumstances such as pollution, temperature ...

snow_cannon_02.jpg
snow_cannon_1041.jpg
snow_cannon_03.jpg
snow_cannon_04.jpg
snow_cannon_05.jpg
snow_cannon_06.jpg

In a ski resort a solenoid valve of a pump station which was used to feed the snow blowers with water failed as shown in this case.

The water was extracted from water reservoirs in higher situated areas and the water pressure was increased to 80 or 100 bar by a pressure booster system in the pump station. Subsequently the water was fed through sometimes very long water pipes to the single consuming units, i.e. the snow blowers.

Problem case:

Due to the failure of the high pressure solenoid valve type 1/041 the high pressure and consequently operation of the snow blowers could not be maintained during the winter season. The control revealed that deposits had been formed on the PTFE sealing surface which resulted in a continuous leakage towards the outlet. However, a small plastic part which had clamped the valve piston was the main reason for valve failure. It is to be assumed that the foreign body had come from the pump station and found its way to the valve despite the filter sieves.