Product data sheet
Valve
B3704-0804-T242-TH-X2,
November 18, 2024
Seat Valve electrically force-controlled
Series A3701-A3706/0804 TH
Valve B3704/0804/.242-TH-X2 AC, DC

The solenoid valve Type 37-TH is used for high temperatures of up to + 180°C (-TH). This valve is suitable for hot water and steam applications in the plant and mechanical engineering. The standard valve is non energized closed - NC. A non energized open -NO design can also be supplied. Temperatureresisting limit switches for both positions, i.e. OPEN and CLOSED can be added on request.

For more information follow this link:
Valve B3704/0804/.242-TH-X2 AC, DC
Link Icon
Datasheet explicit
VersionB
Type of valve37Seat Valve electrically force-controlled
Connection type, valve seat04DN32 32mm
Kv-value (Δp = 1 bar H₂O)28 m³/h
Housing08AISI 316 Ti - 1.4571(81) | AISI 316 Ti - 1.4571(81)
Sealing04PTFE
Voltage type--To be specified later
Solenoid power2426W
Protection class2IP65
Valve optionTH-X2normally closed + Reed contact 2-wire RC27-S + Temperature design
System pressure0 - 25 bar
Valve type12V, 24V, 48V, 110V, 120V, 220V, 230V, AC, DC
Temperature Mediumfrom -40 °C to 180 °C
Temperature Environmentfrom -40 °C to 40 °C
Mounting positionPipeline horizontal, Actuator vertical up
Specific use caseClosed system (includes open system)
scope of delivery1 valve, 1 separate rectifier B0046.0000015 | 1 Solenoid T242 KT05124XX Steel | Terminal box M16x1,5 | 100%ED | Cable clamping range 5 - 10mm | Valve MatchCode G0xx.xxxxxx.0xx.0R1.0xx | Valve MatchCode G0xx.xxxxxx.0xx.099.0xx |
Valve optionTH-X2normally closed + Reed contact 2-wire RC27-S + Temperature design
DescriptionValve opens with continuous voltage | Reed contact | RC27-S Art. B0044.000389 | Contact type: normally open contact | place of install.: top/bottom | Valve position: OPEN and CLOSE | Connector DIN EN 43650 Form C Art. B0040.000097
REACH-RoHS conformityREACH Yes | RoHS Yes
Customs exportCustoms tariff number 84818073; Country of origin Germany; ECCN (US): N; AL: N