Product data sheet
Valve
A2308-0302-5401-CH,
November 18, 2024
Seat Valve electr. direct
Series A23-03 EN161 GGG-40 4bar Gas EU/2016/426
Valve A2308/0302/5401-CH AC

Solenoid valves as safety shut-off devices class A, group 2 according to DIN EN161 with EU type examination EU/2016/426 are used as automatic shut-off valves for securing, limiting, shutting off and releasing the gas and air supply at main shut-offs or in front of gas burners. The valves are suitable for the following gases: Gases corresponding to gas families according to DIN EN 437, gases of the 1st, 2nd and 3rd gas family according to G260.

For more information follow this link:
Valve A2308/0302/5401-CH AC
Link Icon
Datasheet explicit
VersionA
Type of valve23Seat Valve electr. direct
Connection type, valve seat08DN80 80mm
Kv-value (Δp = 1 bar H₂O)94 m³/h
Housing03EN-JS1025 ductile iron
Sealing02FKM
Voltage type5AC
Solenoid power40200W/20W
Protection class1IP54
Valve optionCHnormally closed + EN161 - Gas EU type examination
System pressure0 - 4 bar
Valve type12V, 24V, 48V, 110V, 120V, 220V, 230V, AC
Temperature Mediumfrom -10 °C to 60 °C
Temperature Environmentfrom -10 °C to 60 °C
Mounting positionActuator in vertically or horizontal position
Specific use caseClosed system (includes open system)
scope of delivery1 valve, 1 Solenoid | 200W pickup- | 20W holding winding | M20x1,5 |
Valve optionCHnormally closed + EN161 - Gas EU type examination
DescriptionValve opens with continuous voltage | EC-type aproval with product ident-no. and CE-Marking in conformance with EC-Gas Appliances Regulation (EU/2016/426)
REACH-RoHS conformityREACH Yes | RoHS Yes
Customs exportCustoms tariff number 84818071; Country of origin Germany; ECCN (US): N; AL: N
Not applicable